- Sensitivity & calibration tester as required by AS1851 maintenance testing standard
- The kit comes complete in carry bag and will fit onto any SOLO fibreglass poles
Operating parameters:
- Maximum working height: 6.3m
- Average test time: 120 seconds (1%/ft/minute fast ramp, 0.5%/ft/minute slow ramp)
- Average calibration time:* 40 seconds
- Average clearing time:* 120 seconds
- Average tests per aerosol/canister 100 tests
- Maximum obscuration for ionization: 4.00 %/ft
- Maximum obscuration for photoelectric: 6.00 %/ft
- Resolution: 0.01 %/ft
- Average battery life: 8-10 hours testing on a full charge
Note: *can be conducted whilst walking between detectors
Type of aerosol:
- Environmentally friendly, non-flammable, non toxic.
- A Safety Data Sheet is available on request.
Calibration & servicing:
- In operation: Self-calibrates before each test
- Servicing intervals: 1 year recommended, but max interval 5000 tests
Environment:
- Operating temperature: +10°C to +35°C
- Storage temperature: -10°C to +50°C (Do not store in direct sunlight)
- Humidity: 0-85% RH non-condensing
- Weight of main unit (incl. aerosol canister): 3kg
Because our policy is one of continuous improvement, details described within this publication are subject to change without notice.